LOCHSE Safety sharing 01-June-2023

Published on Slideshow
Static slideshow
Download PDF version
Download PDF version
Embed video
Share video
Ask about this video

Scene 1 (0s)

[Virtual Presenter] LOCHSE Safety sharing 01-June-2023 Safety concern for sampling point at CPF2 Train 3&4.

Scene 2 (14s)

[Audio] 1st Stage separator/2nd stage Separator Outlet Gas Sample Train ¾ Condition: All flexible hose doesn't have safety chain. No platform ladder for sample accessibility. Sample elevation equal eye level. Hazard: High location and monkey ladder. For 2nd stage separator even worse , should climb 2 monkey ladder to reach the sample point. Waiving in case any connection dislodge while operation @ 12 bar pressure..

Scene 3 (55s)

[Audio] Charge Pump Crude Oil Sample Train 3/4 Condition: All flexible hose doesn't have safety chain . Cooling sample loop not connected. Hazards: Waiving in case any connection dislodge / malfunction while operating at 12 bar pressure and temperature of >100°C. High temperature above (70 deg C) sample should equip with permanent line of cooling water..

Scene 4 (1m 33s)

[Audio] Outlet Dehydrator Crude Oil Sample Train 3/4 Condition: Sample point allocated on the top vessel. No platform ladder for sample accessibility. All flexible hose doesn't have safety chain. Cooling sample loop not connected. Hazards: Carry up & down with Sample Cylinder while using monkey ladder will cause safety concern. Waiving in case any connection dislodge / malfunction while operating at high pressure. High temperature above (70 deg C) sample should equip with permanent line of cooling water..

Scene 5 (2m 18s)

[Audio] . 5. Desalter Outlet Crude Oil Sample Train 3/4.

Scene 6 (2m 39s)

[Audio] . THANK YOU ... Internal.