[Audio] Welcome to the presentation basic training for Make Up Water Pump System. This make up water pump system base on model at B3 building. GRUNDFOS Hydro MPC -E Operation & Maintenance Training.
[Audio] 1. Introduction Make-up water pump (MUWP) purpose is to ensure that the water level of the cooling tower is constantly being top up and replenished due to evaporation losses of the cooling tower. This presentation slide explains the overall concept, function, operation and the recommended maintenance of the Make Up Water Pump system..
[Audio] 2. Variable Speed Makeup water pump System –Hydro MPC E The systems supplied are : Make up water pump (MUWP) System 01 and 02 Hydro MPC 4 x CR64-2-1(11kW, 200L tank, 4" SS manifold) Variable speed drive starter control panel Figure above shows the sample of Hydro MPC multi pump system.
[Audio] 3.Layout drawing for Ground Floor Make Up Water Pump Room Equipment Code 1) MY06-M-C-GF-MUWRM-MUWPMP01(MY06-M-C-MWT-G-MUWP-01-1 to 01-4) 2) MY06-M-C-GF-MUWRM-MUWPMP02(MY06-M-C-MWT-G-MUWP-02-1 to 02-4).
[Audio] 4. Detail of individual pump type CR vertical multistage pump Motor High Efficiency IE3 High performance hydraulics Grundfos state-of-the-art hydraulic design and production technology High performance hydraulics Grundfos state-of-the-art hydraulic design and production technology High performance hydraulics Grundfos state-of-the-art hydraulic design and production technology Outlet Inlet.
[Audio] 5. Dimensions detail of Hydro MPC 4 x CR64-2-1.
[Audio] 6. Configuration of Makeup water pump set A and B - Each system have 4 duty Vertical multistage centrifugal pump mounted on mild steel baseplate . - Makeup water pump system A and B takes turn on 12 hour basis. - The duty pump set system run 1st pump with variable speed to maintain at the setpoint pressure. - Once setpoint pressure is achieved and maintained, pump speed will be maintained as well. - Should there be pressure drop, controller will then increase 1st pump operating speed to higher in order to achieve the setpoint pressure. - Once 1st pump speed higher than 98%, 2nd pump will start to operate and both 1st and 2nd pump will then operates with variables speed in order to maintain the setpoint pressure. - Should there be further pressure drop the 3rd pump will the start to operate in order to maintain the constant discharge pressure. - Should there be further pressure drop the 4th pump will the start to operate in order to maintain the constant discharge pressure. - The priority pump selected to run is based on shortest running time. The priority will skip if the pump is trip/fault..
[Audio] 7.Hydro-MPC (Multi Pump Control) Type of System : Variable Speed Pressure Boosting System DOMESTIC WATER SUPPLY PUMP SYSTEM VSD Control : Variable Speed Driver controls the rotation speed of the pump by adjusting the frequency System Model : GRUNDFOS Hydro MPC-E 4 x CR 64-2-1c/w 11 kW 4 duty pump system All pumps in system are with EXTERNAL frequency inverter providing FULL variable speed operation..
[Audio] 8.Control Panel for Domestic Water System (4 x11kW).
[Audio] 9.Human Machine Interface (HMI) – CU 352.
Green supply chain Reduced carbon footprint Waste reduction Water conservation.